FOX Medium Voltage Switchgear

MV Switchgear
Summary

FOX SF6 gas-insulated ring main unit is a licensed product from Schneider Electric. It is primarily used as a ring main unit in distribution networks or for end-user power distribution. It is also commonly used in compact substations and switching stations.
It includes the following protection schemes:

  • Transformer protection via fuses (Q scheme);
  • Transformer protection via vacuum circuit breakers (B scheme);
  • FOX-NE compact type: features compact dimensions and a small footprint, easy to install in distribution rooms;
  • FOX-DE expandable/modular type: the modular design facilitates expansion, allowing connection on either the left or right side.
Dimension

Cabinet height: 1800mm;

Cabinet width: 375mm (standard panel) / 500mm (CB unit);

Cabinet depth: 840mm;

Structural Characteristics
  • SF6 gas insulated, unaffected by external environmental conditions;
  • Flexible and diverse combination schemes;
  • Small volume and compact structure;
  • Mimic diagram on the operation interface, providing clear and visible switch position indication;
  • Interrogatory mechanical interlocking system prevents incorrect operation;
  • 30-year service life with maintenance-free main circuit during the lifetime.
Standards Compliant
  • GB3906-2020 "3.6~40.5kV AC Metal-Enclosed Switchgear and Controlgear";
  • IEC60529 Degrees of protection provided by enclosures (IP Code);
  • IEC62271-100 High-voltage circuit breakers and switch-fuse combinations;
  • IEC62271-102 Disconnectors and earthing switches;
  • IEC62271-200 AC metal-enclosed switchgear and controlgear for indoor installation.
Technical Parameter
  • Rated current: 630A;
  • Rated voltage: 12KV; Rated short-circuit breaking current: 20/25KA;
  • Rated short-circuit making current: 50/63KA;
  • 1min power-frequency withstand voltage: 42/48KV;
  • Lightning impulse withstand voltage: 75/85KV;
  • Enclosure protection degree: IP3X; Gas tank protection degree: IP67;
  • Annual leakage rate: ≤0.1%;
  • Mechanical life of load switch: 5000 operations; Earthing switch: 3000 operations;
Application
  • Indoor ambient air temperature: -25~40℃;
  • Indoor altitude for operation: ≤2000m;
  • Relative humidity of ambient air: ≤90% (+25℃);
  • Inclination from the vertical plane: ≤5°;
  • Seismic intensity not exceeding 8°, non-polluted, no severe vibration sites;
  • Pollution class: Class II; Class III for coastal/industrial areas.