MV Switchgear
Summary
FOX SF6 gas-insulated ring main unit is a licensed product from Schneider Electric. It is primarily used as a ring main unit in distribution networks or for end-user power distribution. It is also commonly used in compact substations and switching stations.
It includes the following protection schemes:
- Transformer protection via fuses (Q scheme);
- Transformer protection via vacuum circuit breakers (B scheme);
- FOX-NE compact type: features compact dimensions and a small footprint, easy to install in distribution rooms;
- FOX-DE expandable/modular type: the modular design facilitates expansion, allowing connection on either the left or right side.
Dimension
Cabinet height: 1800mm;
Cabinet width: 375mm (standard panel) / 500mm (CB unit);
Cabinet depth: 840mm;
Structural Characteristics
- SF6 gas insulated, unaffected by external environmental conditions;
- Flexible and diverse combination schemes;
- Small volume and compact structure;
- Mimic diagram on the operation interface, providing clear and visible switch position indication;
- Interrogatory mechanical interlocking system prevents incorrect operation;
- 30-year service life with maintenance-free main circuit during the lifetime.
Standards Compliant
- GB3906-2020 "3.6~40.5kV AC Metal-Enclosed Switchgear and Controlgear";
- IEC60529 Degrees of protection provided by enclosures (IP Code);
- IEC62271-100 High-voltage circuit breakers and switch-fuse combinations;
- IEC62271-102 Disconnectors and earthing switches;
- IEC62271-200 AC metal-enclosed switchgear and controlgear for indoor installation.
Technical Parameter
- Rated current: 630A;
- Rated voltage: 12KV; Rated short-circuit breaking current: 20/25KA;
- Rated short-circuit making current: 50/63KA;
- 1min power-frequency withstand voltage: 42/48KV;
- Lightning impulse withstand voltage: 75/85KV;
- Enclosure protection degree: IP3X; Gas tank protection degree: IP67;
- Annual leakage rate: ≤0.1%;
- Mechanical life of load switch: 5000 operations; Earthing switch: 3000 operations;
Application
- Indoor ambient air temperature: -25~40℃;
- Indoor altitude for operation: ≤2000m;
- Relative humidity of ambient air: ≤90% (+25℃);
- Inclination from the vertical plane: ≤5°;
- Seismic intensity not exceeding 8°, non-polluted, no severe vibration sites;
- Pollution class: Class II; Class III for coastal/industrial areas.